BREAKER CIRCUIT P/N KA36200

NSN Number : 5925 01 181 2995 Category :

$1,588.00

Part Number: 5925 01 181 2995

Manufacturer: SQUARE D CO

Manufacturer's Product Number: 5925 01 181 2995

Condition: New

2 in stock

BREAKER CIRCUIT
P/N KA36200
PN JJA36200
NSN 5925-01-181-2995
MFG SQUARE D CO
NEW GOV SURPLUS
SUPPLIER CAGE CODE 03EF7
ITEM NAME: CIRCUIT BREAKER
DEFINITION: A device with means other than fuses for automatically opening the

circuit in which it is installed when the current varies from the

predetermined value for which the device is set. May include

provisions for manual operation. At least one set of contacts must be

in series with the actuating element(s). A combination of

semiconductor and passive devices may be used in lieu of contacts. For

automatically operated items in which the actuating (tripping) element

and contacts are not in series, see RELAY (as modified). For items

which are operated both manually and automatically but the actuating

elements and contact are not in series, see RELAY-SWITCH. Excludes

CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH

(as modified); and CONTROLLER.


CHARACTERISTIC VALUE
BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
BODY LENGTH 8.000 INCHES NOMINAL
BODY WIDTH 4.500 INCHES NOMINAL
BODY HEIGHT 3.500 INCHES NOMINAL
CASE MATERIAL PLASTIC
CENTER TO CENTER DISTANCE 6.562 INCHES NOMINAL
BETWEEN TERMINALS PARALLEL
TO LENGTH
CENTER TO CENTER DISTANCE 1.500 INCHES NOMINAL
BETWEEN TERMINALS PARALLEL
TO WIDTH
UNTHREADED MOUNTING HOLE 0.203 INCHES NOMINAL
DIAMETER
DISTANCE BETWEEN 7.125 INCHES NOMINAL
CENTERLINES OF MOUNTING
FACILITIES PARALLEL TO BODY
LENGTH
DISTANCE BETWEEN 1.500 INCHES NOMINAL
CENTERLINES OF MOUNTING
FACILITIES PARALLEL TO BODY
WIDTH
BOSS HEIGHT 0.156 INCHES NOMINAL
POLE QUANTITY 3
MOUNTING FACILITY TYPE AND 4 UNTHREADED HOLE
QUANTITY III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
MAXIMUM CONTINUOUS LOAD 200.0 AMPERES AC AND 200.0 AMPERES DC ALL
CURRENT RATING PER POLE LOCATIONS
OPERATING VOLTAGE TYPE AND 600.0 AC AND 250.0 DC ALL LOCATIONS
RATING PER POLE IN VOLTS
MAXIMUM INTERRUPTING 22000.0 AC AND 10000.0 DC ALL LOCATIONS
CAPACITY CURRENT TYPE AND
RATING PER POLE IN AMPS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC INSTANTANEOUS AND TIME DELAY ALL LOCATIONS
ULTIMATE TRIP RATING OF 140.0 ALL LOCATIONS
CONTINUOUS CURRENT RATING
PER POLE IN PERCENT
RESET METHOD MANUAL
MAIN CONTACT TRIPPING TRIP FREE
MECHANISM TYPE
MANUAL ACTUATOR TYPE AND 1 TOGGLE
QUANTITY
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION AT POLE TWO
DESIGNATION
TRIP DELAY TIME IN SECONDS 25.000 MINIMUM AT 200 PCT AND 200.000 MAXIMUM AT
PER RATED CONTINUOUS 200 PCT ALL LOCATIONS
CURRENT
INCLOSURE PROTECTION TYPE GENERAL PURPOSE
FOR WHICH DESIGNED
TRIP RELEASE AMBIENT TEMP 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
RATING
FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
TERMINAL TYPE AND QUANTITY 6 COMPRESSION