$175.00
Part Number: 5925 00 539 8372
Manufacturer: GENERAL ELECTRIC COMPANY
Manufacturer's Product Number: 5925 00 539 8372
Condition: New
7 in stock
CIRCUIT BREAKER
P/N TED134100
NSN 5925-00-539-8372
MFG GENERAL ELECTRIC
NEW GOV SURPLUS
SUPPLIER CAGE CODE 03EF7
ITEM NAME: CIRCUIT BREAKER
DEFINITION: A device with means other than fuses for automatically opening the
circuit in which it is installed when the current varies from the
predetermined value for which the device is set. May include
provisions for manual operation. At least one set of contacts must be
in series with the actuating element(s). A combination of
semiconductor and passive devices may be used in lieu of contacts. For
automatically operated items in which the actuating (tripping) element
and contacts are not in series, see RELAY (as modified). For items
which are operated both manually and automatically but the actuating
elements and contact are not in series, see RELAY-SWITCH. Excludes
CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH
(as modified); and CONTROLLER.
CHARACTERISTIC VALUE
BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
BODY LENGTH 6.312 INCHES NOMINAL
BODY WIDTH 4.125 INCHES NOMINAL
BODY HEIGHT 3.187 INCHES NOMINAL
CASE MATERIAL PLASTIC
CENTER TO CENTER DISTANCE 4.875 INCHES NOMINAL
BETWEEN TERMINALS PARALLEL
TO LENGTH
CENTER TO CENTER DISTANCE 1.375 INCHES NOMINAL
BETWEEN TERMINALS PARALLEL
TO WIDTH
UNTHREADED MOUNTING HOLE 0.188 INCHES NOMINAL
DIAMETER
DISTANCE BETWEEN 4.875 INCHES NOMINAL
CENTERLINES OF MOUNTING
FACILITIES PARALLEL TO BODY
LENGTH
DISTANCE BETWEEN 1.375 INCHES NOMINAL
CENTERLINES OF MOUNTING
FACILITIES PARALLEL TO BODY
WIDTH
BOSS HEIGHT 0.240 INCHES NOMINAL
POLE QUANTITY 3
MOUNTING FACILITY TYPE AND 4 UNTHREADED HOLE
QUANTITY
III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
MAXIMUM CONTINUOUS LOAD 100.0 AMPERES AC ALL LOCATIONS
CURRENT RATING PER POLE
OPERATING VOLTAGE TYPE AND 480.0 AC ALL LOCATIONS
RATING PER POLE IN VOLTS
MAXIMUM INTERRUPTING 14000.0 AC ALL LOCATIONS
CAPACITY CURRENT TYPE AND
RATING PER POLE IN AMPS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
ULTIMATE TRIP RATING OF 125.0 ALL LOCATIONS
CONTINUOUS CURRENT RATING
PER POLE IN PERCENT
RESET METHOD MANUAL
MAIN CONTACT TRIPPING TRIP FREE
MECHANISM TYPE
MANUAL ACTUATOR TYPE AND 1 TOGGLE
QUANTITY
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION AT POLE TWO
DESIGNATION
TRIP DELAY TIME IN SECONDS 84.000 MINIMUM AT 200 PCT AND 360.000 MAXIMUM AT
PER RATED CONTINUOUS 200 PCT ALL LOCATIONS
CURRENT
INCLOSURE PROTECTION TYPE FUNGUS RESISTANT
FOR WHICH DESIGNED
TRIP RELEASE AMBIENT TEMP 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
RATING
FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
TERMINAL TYPE AND QUANTITY 6 COMPRESSION